Beijing Ruibaili exclusive pioneer sewage full liquid heat pump

In order to solve the problem of sewage corrosion of heat pump units, recently, Ruiboli Thermal Technology Co., Ltd. has independently developed a full liquid sewage pump heat pump (Patent No .: 2010101221319), referred to as sewage source heat pump units.

Ruibao independent research and development: sewage dedicated full liquid heat pump


working principle


1 compressor, 2 oil separator, 3 condenser, 4 electronic expansion valve,

5 evaporator; 6 economizer; 7 intelligent sewage resistance machine; 8 ~ 19 tangential valve;

Cooling principle: tangential valves 9,10,13,14 open, 8,11,12,15 is closed, the refrigerant absorbs heat in the evaporator evaporation, the system made of 7 ℃ cold water into the room to use, the refrigerant then Compressor compressed into high temperature and pressure superheated steam into the condenser, remove the heat from the sewage and back to the sewage trunk.

Heating principle: tangential valves 9,10,13,14 closed, 8,11,12,15 open, the evaporator into a condenser, the condenser into an evaporator. The refrigerant absorbs the heat of the sewage in the evaporator and evaporates, and the sewage is returned to the trunk of the sewage. The refrigerant is compressed into high-temperature and high-pressure superheated steam into the condenser by the compressor to heat the circulating water to prepare hot water (temperature 45 ~ 50 ℃, high temperature 60 ℃).

work process

The sewage is promoted to a machine room by a sewage pump, after being filtered by a smart sewage anti-resistance machine, enters a sewage source heat pump unit; after being warmed (or cooled) by the heat pump unit, the sewage again flows through the intelligent sewage anti-resistance machine and carries the contaminants Back to the trunk of the sewage. Heat pump unit to the end of the system for cooling (or heating).

Features

Wastewater dedicated liquid-filled unit of the sewage side of the heat exchanger, the heat pipe material for the Navy copper. The unit uses six specialized technologies to improve unit performance.

(1) Spray (falling film) evaporator, effectively improve the evaporation temperature of the unit;

(2) dedicated jet pump in the state of no energy consumption, complete the system of continuous oil return, safe and reliable;

(3) specially designed high-performance condenser, which can reduce the condensing temperature of the unit;

(4) the use of two compressor technology (used in high temperature water source heat pump);

(5) a unique configuration of the oil separator and flicker-type energy-saving device;

(6) the use of low pressure booster technology - exclusive first.

Among them, the spray evaporator + high-performance heat transfer tube + low-pressure booster technology = increase the evaporation temperature;

Secondary compression technology + increase the evaporation temperature = increase the cooling capacity (Qc);

Unique condenser design + high-performance heat transfer tube = lower condensation temperature;

Reduce condensing temperature + selection of dedicated compressor volume ratio = lower compressor work (N).

Applications

This product is used in the direct system. It can be used with the self-developed sewage anti-friction machine. The energy-saving effect is more obvious, the COP value is significantly increased, and the initial investment cost and the operation cost can be reduced in the early stage.